CODESYS OPC UA Server SL Article no. 2302000041
The OPC UA
Server exposes variables configured in the symbolic configuration of a CODESYS
project to the OPC UA address space. Clients can read, write and monitor the
values of the PLC. To enable the OPC UA support in the CODESYS Development
System the option “Support OPC UA Features” must be set in the symbol
configuration.
Also see
[CODESYS Online Help](https://help.codesys.com/webapp/_cds_runtime_opc_ua_server;product=codesys).
The OPC
UA Server supports the following features:
Browsing of
data types and variables
Standard
read/write services
Notification
for value changes (subscription and monitored item services)
No
restriction in the number of sessions, monitored items, and subscriptions (the
number depends on the performance of the respective platform)
Support of
events
Support of
complete access to structures
Encrypted
communication with an OPC UA Client
Support of
multitasking
Support of
OPC UA methods
Support of
Alarms&Conditons
Supported
profiles: Currently
the OPC UA server supports the “Micro Embedded Device Server Profile”. This
server profile allows reading, writing, and subscribing of items.
Supported
information models: OPC UA allows defining different data types. The
combination of customer defined data types, object types and reference types
allows defining your own information model. An information model describes how
the data should be exposed to the address space.
PLCopen
information model
User-defined
information models (companion specifications)
Also see
[CODESYS Online Help](https://help.codesys.com/webapp/_cds_using_opc_ua_information_models;product=codesys).
Security: *
X.509 based communication * User management
SecurityProfiles:
- None - Basic256Sha256 (Sign, Sign_and_Encrypt) - Aes128_Sha256_RsaOaep -
Aes256_Sha256_RsaPss
User token
policy: - Anonymouse - Username